• 产品名称: ACP 6000
  • 产品编号: 柔性AC电流传感器 ACP 6000
  • 产品概况 ACP 6000The ACP 6000_3 is an AC current Probe utilising the Rogowskiprinciple. It can be used to measure currents up to 6000 Amps fromvery low frequencies to 10kHz.The flexible and lightweight measuring head allows quick and easyinstallation in hard to reach areas and with large conductors.

ACP 6000

The ACP 6000_3 is an AC current Probe utilising the Rogowski

principle. It can be used to measure currents up to 6000 Amps from

very low frequencies to 10kHz.

The flexible and lightweight measuring head allows quick and easy

installation in hard to reach areas and with large conductors.

ACP 6000

Electrical Characteristics

Current Ranges (selectable via rotary switch) .......... : 60A / 600A / 6000A ACRMS

Output Sensitivity (AC coupled) ................................ : 50mV / 5mV / 0.5mV per A

Accuracy (at 25°C) .................................................... : ± 1% of reading ± 0.1A (60A range)

................................................................................... : ± 1% of reading ± 1A (600A / 6000A range)

Load Impedance ........................................................ : 100kΩ minimum

Linearity (10% to 100% of range) ............................. : ± 0.2% of reading

Noise ......................................................................... : 80mA (60A) / 400mA (600A / 6000A range)

Bandwidth (-1dB) ....................................................... : 10Hz to 10kHz

Phase Error (45 – 65Hz) ........................................... : ± <1º

Temperature Coefficient ............................................ : ± 0.1% of reading / °C

Position Sensitivity .................................................... : ± 2% of reading

External Field (with cable > 100mm from the head) . : ± 0.2% of range

Power Supply ............................................................ : 2 x AA MN 1500 LR6 Alkaline

................................................................................... : 2000 hours, low battery indicator

................................................................................... : external power supply (3V / 100mA)

Overload Indication ................................................... : Red LED ON indicates the range overload

Working Voltage (see Safety Standards section) ..... : 1000V AC RMS or DC (Probe and Integrator)

................................................................................... : 30V max (Output)

ACP 6000

General Characteristics

Probe and Cable Material ......................................... : Alcryn 2070 NC, LATENE 7H2W V0

Probe Cable Length (s) ............................................. : 610mm (24”) / 915mm (36”) / 1220mm (48”) / 2490mm (98”)

Probe Cable Diameter ............................................... : 9.9 mm (nominal)

Cable Length (Probe to Integrator box) .................... : 2 m

Output ........................................................................ : 0.5m long lead terminated with

................................................................................... : a safety male BNC

Operating Temperature Range ................................. : -20 to +65°C

Storage Temperature Range .................................... : -40 to +75°C

Operating Humidity.................................................... : 15% to 85% (non condensing)

Degree of protection .................................................. : IP65 Probe, IP40 Integrator module

Colour ........................................................................ : RAL 120 70 75 Lemon green,